Electric cables. Thermosetting insulated, armoured cables of rated voltages of 600/1 000 V and 1 900/3 300 V for fixed installations, having low emission of smoke and corrosive gases when affected by fire. Specification
standard by BSI Group, 02/28/2017

Format: PDF      In Stock

 

Category:

NOTE: Our website provide PDF immediately download, sometimes when the payment is processed and you did not receive the file, please feel free to connect with us.

Description

BS 6724:2016 specifies requirements for the construction andperformance of thermosetting insulated, armoured cables of rated voltagesof 600/1 000 V and 1 900/3 300 V, having low emission of smoke and corrosivegases when affected by fire.

NOTE 1 Other thermosetting insulated, armoured cables for voltages of 600/1 000 Vand 1 900/3 300 V can be found in BS 5467, but these do not have low levels ofemission of smoke and corrosive products under exposure to fire.

This British Standard is applicable to cables for use in fixed installations inindustrial areas, buildings or similar applications.

This British Standard specifies requirements for the following types of cables:

  • 600/1 000 V cables, wire armoured and oversheathed having single-core,two-, three-, four- and five-core stranded copper conductor;
  • 600/1 000 V multicore auxiliary cables, wire armoured, and oversheathed,stranded copper conductor; and
  • 1 900/3 300 V cables, wire armoured and oversheathed, having single-coreor three-core stranded copper conductor.

This British Standard is applicable to cables that are designed for a maximumsustained conductor temperature of 90 °C and for a maximum short-circuitconductor temperature of 250 °C (for a maximum of 5 s).

NOTE 2 Limitation on the temperature of the cables may be imposed in situationswhere they might be touched or where they could touch other materials.

NOTE 3 Annex A gives a guide to the use and installation of cables, Annex B givesarmour wire tests, Annex C gives a compatibility test, Annex D gives an abrasionresistance test, Annex E gives an insulation resistance constant test on oversheath,Annex F gives the resistance of conductor and armour, Annex G gives the grosscross-sectional area of armour, Annex H gives a test for shrinkage of oversheath oncable, Annex I gives guidance on type tests and Annex J gives the standard UnitedKingdom reference codes.

Cross References:
BS 7655-1.2
BS 7655-1.3
BS 7655-6.1
BS EN 10244-2:2009
BS EN 50363-5
BS EN 50395
BS EN 50396
BS EN 60228
BS EN 60229
BS EN 60332-1-2:2004+A1:2015
BS EN 60332-3-24:2009
BS EN 60754-1
BS EN 60811-401
BS EN 60811-501
BS EN 60811-502
BS EN 61034-2
BS EN 62230
BS EN ISO 6892-1
IEC 60050-461
BS 5467
BS 7671:2008+A3:2015
BS 8512
BS 8573:2012
BS EN 50262
BS EN 50393
BS EN 60079-14
BS EN 61914
BS EN 62275
BS EN 62444
IEC 60183
Electricity Safety, Quality and Continuity Regulations
2002

Replaces BS 6724:1997+A3:2008 which remains current